A3716 16+ Channel Online Monitoring System

A3716 16+ Channel Online Monitoring System

 

The A3716 is powerful online monitoring system for rotating machinery. The A3716 system can operate as an independent monitoring system or it can be used as extension of an existing protection system. The A3716 module contains 16 AC, 16 DC and 4 TACHO inputs. All channels are measured simultaneously. The A3716 modules can be easily composed together and by this we can create system with more channels.

The setting and control of A3716 is done in DDS software. The setting has never been easier. The only thing you need to do is to create the tree of machines, measurement points,required readings and assign them to appropriate channels. Then you just press START and the readings are done automatically.

 

 

[no_unordered_list style=”circle” number_type=”circle_number” animate=”yes” font_weight=”normal”]

Key Features:

  • Adaptive algorithm of data acquisition
  • 16 channels AC (ICP®)
  • 16 channels DC
  • 4 TACHO inputs
  • 16 BNC buffered outputs of signals from sensors
  • 16 programmable relays outputs

[/no_unordered_list]

 

 

Application Scheme of A3716 Units

 

A3716 application scheme

 

 

Technical Performance
Input channels AC: 16 x AC, ICP® power supply on/off
input impedance 100kΩ
integration single, double
high pass filter 1 Hz – 12800 Hz
low pass filter 25 Hz – 25600 Hz
Input channels DC: 16 x DC for process values
input impedance 100 kΩ (VDC), 250 Ω (mADC)
TACHO inputs: 4 independent TACHO for speed probe / external trigger
speed range 0,8 Hz – 1000 Hz
Input range: AC +/- 12 V peak-peak
DC +/- 24 V or 4 – 20 mA
TACHO +10V
AD conversion: 24 bit, 64 bit double floating point internal signal processing
No AutoGain function!
Dynamic range S/N: 120 dB
Frequency ranges: max. 25,6 kHz (16 Ch, 65,5 kHz sampling)
Sampling mode: Fully simultaneous for 16 channels
FFT resolution: Min. 100 lines
Max. 25 600 lines
Processor: Intel Core2 – 2.5 GHz
Memory RAM: 4 GB
Internal hard drive: SSD 128GB
Data acquisition: Overall values
Time signals
FFT real time analysis
DEMOD – ENVELOPE analysis
ACMT – low speed bearing analysis
order analysis
user band pass analysis
RPM measurement
DC measurement
Orbit measurement
Speed measurement
Signal Recorder: 64 kHz sampling frequency
4 Ch memory consumption 3 GB/hour
Trigger: free run, TACHO, external (voltage)
Communication: Ethernet 1GB RJ45
Temperature range: -10˚C to +50˚C
Power: AC 110 – 240 V, 45 – 65 Hz
Case: 19´´aluminium rack
Size & Weight (2U): 430 x 360 x 90 mm
4,7 kg
Size & Weight (3U): 430 x 360 x 135 mm
6,2 kg

 

 

Adaptive Algorithm of Data Acquisition

[no_unordered_list style=”circle” number_type=”circle_number” animate=”yes” font_weight=”normal”]

 

Conventional Model of Data Acquisition (used by various brands):

  • Data was measured in defined time interval (e.g. every minute), so they were not measured continuously, so some important value changes in between those measurements have been lost
  • Every measured data was saved, so the values with no information (same value as before) were saved and they took valuable space

 

Adaptive Algorithm of Data Acquisition (new Adash system):

  • Data are measured continuously, so you cannot miss anything
  • Only selected values are saved. If the measured value is not changing significantly, it is not saved. Adaptive Algorithm selects which data to save and which not.

NOTE:
The volume of possible data saved is highly reduced in this way, so it ensures that saved data cannot take too much space and the access to the database is not slowed down (otherwise it would be). There is no need to purchase expensive SQL servers. There is database solution provided in DDS software, which controls the A3716 units. You can run the database system on the standard laptop.

 

 

How Adaptive Algorithm selects which data to save and which not?

  • Adaptive Algorithm measures data continuously and it does not save the values which do not change significantly. It saves only those values which changes from the previous one more than e.g. 5%, so if the measured value does not change significantly, the system does not save it.
  • Only selected values are saved. If the measured value is not changing significantly, it is not saved. Adaptive Algorithm selects which data to save and which not.

NOTE:
No diagnostician needs the values with change with less than 5% recorded, see the pictures below.

  • There is time interval for data saving determined, so if this interval is set to 1 hour and a values do not change significantly for e.g. 1 hour, it is saved after 1 hour anyway).
  • Adaptive Algorithm can change some of its parameters on its own, so the data saving is optimized, e.g. for the process with very variable values it can increase the percentage value of significant change (e.g. from 5% to 10%) determining which measured values are saved. See the picture below how it affects acquired results.

[/no_unordered_list]

 

All data saved:

A3716 adaptive algorithm of data acquisition

 

Significant change = 5 %

A3716 adaptive algorithm of data acquisition - significant change 5 %

 

Significant change = 10 %

A3716 adaptive algorithm of data acquisition - significant change 5 %

 

Significant change = 20 %

A3716 adaptive algorithm of data acquisition - significant change 5 %

 

Significant change = 50 %

A3716 adaptive algorithm of data acquisition - significant change 5 %

You may also like…