HS-422 Transmitter 4-20mA velocity- 2 Pin MS
Vibration Monitoring with Hansford Sensors
Our advanced vibration transmitters, or loop powered sensors, are engineered for use with the latest PLC (programmable logic controller), BMS (building management system), or SCADA (supervisory control and data acquisition) technologies, offering sophisticated solutions for condition monitoring and preventative maintenance.
The family is available with a variety of different cables.
Key Features:
[no_unordered_list style=”circle” number_type=”circle_number” animate=”yes” font_weight=”normal”]
- 4-20mA output proportional to ‘g’
- Various mountings
- Sealed to IP68
[/no_unordered_list]
Typical Applications:
Fans, pumps, motors, gearboxes, compressore, centrifuges, conveyors, Air handlers, rolls, dryers, presses, cooling, VAC, spindles, machine tooling, process equipment
Technical Performance |
---|
Mounted Base Resonance: 10kHz min |
Velocity Ranges: see: ‘How To Order’ table ± 10% Nominal 80Hz at 22°C |
Frequency Response: 10Hz (600cpm) to 5kHz (300kcpm) ± 5% – ISO10816 |
Isolation: Base isolated |
Range: see: ‘How To Order’ table |
Transverse Sensitivity: Less than 5% |
Mechanical |
---|
Case Material: Stainless Steel |
Sensing Element/Construction: PZT/Compression |
Mounting Torque: 8Nm |
Weight: 150gms (nominal) |
Sheilded Cable Assembly: see: www.hansfordsensors.com for options |
Mounting Threads: see: ‘How To Order’ table |
Electrical |
---|
Current Output: 4-20mA DC proportional to acceleration |
Supply Voltage: 15-30 Volts DC (for 4-20mA) |
Settling Time: 2 seconds |
Output Impedance: Loop Resistance 600 Ohms max. at 24 Volts |
Case Isolation: >108 Ohms at 500 Volts |
Environmental |
---|
Operating Temperature Range: -25 to 90ºC |
Sealing: IP68 |
Maximum Shock: 5000g |
EMC: EN61326-1:2013 |
Typical Frequency Response (at 100mV/g):